On November 2, 2025, at 0915 EST, and on November 3, 2025 at 0203 EST, while [Hatch] Unit 1 was at 100-percent power, the normal supply breaker from the `1D' 600V switchgear to the 120/208V essential transformer `1C' tripped on overcurrent due to a ground resulting in the loss of the `1B' essential bus and the `1B' instrument bus. The loss of power impacted the logic of the primary and secondary containment isolation systems resulting in the invalid actuation of containment isolation valves (CIVs) in multiple systems. The ground within the `1D' 600V switchgear was cleared by racking [out] the associated breaker and by replacing a degraded wire. A future action includes performing a detailed cubical and bus bar inspection of the `1D' 600V switchgear.